Designed to provide a simple, fast and cost effective solution for DC power requirements .
Key advantages
Improved reliability | Provided by a fully controlled SCR bridge and a reduced quantity of components |
Adaptability | Thanks to a selection of industrialized options and an easy parameter settings for quick onsite adjustments |
Simplicity | Of the product design to improve MTBF and to reduce MTTR |
Low Voltage Ripple | To optimize battery life |
Low inrush current | < 8In not to oversize mains power supply (3-phase) |
Compact design | With the capability to integrate the battery in the charger cabinet |
Human-Machine Interface (HMI) | To deliver appropriate information level to the user |
Ingress protection | Up to IP55 for harsh environmental conditions |
Compatibility | With nickel-cadmium and lead-acid batteries, vented or gas-recombination types |
Galvanic isolation | Between input and output |
Digital control | Digital control and monitoring |
Wide choice | Wide choice of configurations and options |
Input
Model | 1-Ph: FP40R10 3-Ph: FP40R30 |
Input voltage (other voltage on request) | 1-Ph: 230 VAC ± 10% 3-Ph: 400 VAC ± 10% |
Inrush current | 1-Ph: < 15 ln 3-Ph: < 8 ln |
Frequency range | From 47 to 63 Hz |
Output
Available rating | See ratings table |
Nominal DC voltage | 24/48/110/220V |
Static regulation | 1 % |
Voltage ripple 1-ph | Disconnected battery (< 2.5 %) |
Voltage ripple 3-ph | Disconnected battery (< 0.7 %) |
Supervision
Charger status | Charger status and alarms on displaying Unit |
Displayed values: | Output voltage, output current, battery Current |
Remote signaling | With 4 dry contacts |
Event log | Up to 100 events |
Battery
Type | Lead acid or nickel cadmium, vented or recombination |
Autonomy | From few minutes to several hours, as required |
General data
Rectifier efficiency | From 83 % to 94 % (according to model) |
Operating temperature | From 0 to 40 °C (without system derating) |
Storage temperature | From -20 °C to +70 °C (battery excluded) |
Relative humidity | < 95 % non condensing at 20 °C |
Operating altitude | 1000 m (without system derating) |
Cooling | Natural or fan-assisted (according to rating) |
External ingress protection | IP20 |
Internal protection | Internal protection |
Noise (at 1m in front of the unit) | ≤ 60 dB |
Isolation | Input – Output 2500 VAC / 1 minute |
Frame colour | RAL 7035 or RAL 7032 |
Dimensions | Varying according to ratings and options (consult us) |
Output current (A) vs Output voltage (Vdc)
Ratings with 1-phase input | 24 Vdc: 100A 48 Vdc: 40/60/100A 110-125 Vdc : 25/40/60/100A 220 Vdc: 25A |
Ratings with 3-phase input | 24 Vdc: 35/65/100/160/220/300/400A 48 Vdc: 35/65/100/160/220/220/300/400A 110-125 Vdc: 35/65/100/160/220/300/400A 220 Vdc: 35/65/100/160/220/300A |
Options
Charger | Input circuit breaker or molded case circuit breaker (16 kA or 36 kA) Position contact on AC input circuit breaker Paralleling diode Dropping diode DC earth fault monitor Customer connection on terminal blocks Ultra low voltage ripple < 0.1 % (48 V) Measurements of AC input voltage, current and frequency |
Battery | Battery protection (fuses or circuit breaker with contact) Protection against battery reversed polarity Battery Low Voltage Disconnection (LVD) Battery Low Voltage Disconnection (LVD) Temperature sensor for battery charge compensation Test battery presence or test battery capacity |
Mechanical | Operating temperature up to 55 °C (with system derating) External ingress protection IP21, 23, 40, 41, 43, 55 Space heater with hygrostat and/or thermostat Internal lighting 100 mm or 200 mm base frame Lifting eyes |
DC Load | DC output protection (fuses or circuit breaker with contact) Distribution board (circuit breaker with or without contact) |
Communication | Modbus RS485 Remote alarm up to 8 additional relays |
Special Request
Configuration | Single rectifier with no battery Dual charger in single cabinet Dual charger with shared battery |
Battery | Batteries in charger cabinet (on shelves or drawers) |
Mechanical | Other RAL painting colour |
European Directives
Low voltage directive | 2006/95/EC (before April 2016) 2014/35/EU (after April 2016) |
EMC directive | 2004/108/EC (before April 2016) 2014/30/EU (after April 2016) |
Compliances
IEC/NF EN 60146-1-1: 2009 | Semiconductor converters – Part 1-1: Specification of basic requirements |
IEC/NF EN 61000-6-2: 2006 | Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments |
IEC/NF EN 61000-6-4: 2007 AMD1: 2011 | Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standards for industrial environments |
IEC/NF EN 61439-1: 2012 | Low voltage switchgear and controlgear assemblies – Part1: General rules |
IEC/NF EN 60950-1: 2013 AMD2: 2014 | Information technology equipment – Safety – Part 1: General requirements |
NF C58-311: 1990 | Procedure for type tests for rectifier-battery charger and batteries |